$ $ $ $ $

Pamumuhunan sa Ginto

Nung mga panahon na–ospital ang aking ina, ako ay nangailangan ng cash ng ora–orada! Meron akong pera pero ito ay nasa Stock Market. Pu...

Monday, June 11, 2018

NATIONAL BUILDING CODE OF THE PHILIPPINES (NBCP) part 2


CHAPTER XII

GENERAL DESIGN AND CONSTRUCTION REQUIREMENTS


Section 1201
General Requirements

Buildings proposed for construction shall comply with all the regulations and specifications herein set forth governing quality, characteristics and properties of materials, methods of design and construction, type of occupancy and classification.

All other matters relative to the structural design of all buildings and other structures not provided for in this Chapter shall conform to the provisions of the National Structural Code of Buildings, as adopted and promulgated by the Board of Civil Engineering pursuant to the Republic Act Number 544, as amended, otherwise known as the “Civil Engineering Law”.


Section 1202
Excavation, Foundation and Retaining Walls

(a)   Subject to the provisions of Articles 684 to 686 of the Civil Code of the Philippines on lateral and subjacent support, the design and quality of materials used structurally in excavation, footings, and in foundations shall conform to accepted engineering practice.

(b)   Excavation and Fills

(1) Excavation or fills for buildings or structures shall be so constructed or protected that they do not endanger life or property.

(2) Whenever the depth of excavation for any construction is such that the lateral and subjacent support of the adjoining property or existing structure thereon would be affected in a manner that the stability or safety of the same is endangered, the person undertaking or causing the excavation to be undertaken shall be responsible for the expense of underpinning or extending the foundation or footings of the aforementioned property or structure.

(3) Excavation and other similar disturbances made on public property shall, unless otherwise excluded by the Building Official, be restored immediately to its former condition within 48 hours from the start of such excavation and disturbances by whosoever caused such excavation or disturbance.

(c) Footings, Foundations, and Retaining Walls

(1) Footings and foundations shall be of the appropriate type, of adequate size, and capacity in order to safely sustain the superimposed loads under seismic or any conditions of external forces that may affect the safety or stability of the structure. It shall be the responsibility of the architect and/or engineer to adopt the type and design of the same in accordance with the standards set forth by the Secretary.

(2) Whenever or wherever there exists in the site of the construction an abrupt change in the ground levels or level of the foundation such that instability of the soil could result, retaining walls shall be provided and such shall be of adequate design and type of construction as prescribed by the Secretary.


Section 1203
Veneer

(a) Definition. Veneer is a non structural facing of brick, concrete, tile, metal, plastic, glass, or other similar approved materials attached to a backing or structural components of the building for the purpose of ornamentation, protection, or enclosure that may be adhered, integrated, or anchored either on the interior or exterior of the building or structure.

(b) Design Requirements. The design of all veneer shall comply with the following:

(1) Veneer shall support no load other than its own weight and the vertical dead load of veneer immediately above.

(2) Surfaces to which veneer is attached shall be designed to support the additional vertical and lateral loads imposed by the veneer.

(3)  Consideration shall be given to differential movements of the supports including those caused by temperature changes, shrinkage, creep, and deflection.

(4) Adhered veneer and its backing shall be designed to have a bond to the supporting elements sufficient seismic effects on the total assemblage.

(5) Anchored veneer and its attachment shall be designed to resist horizontal forces equal to twice the weight of the veneer.

(6) Anchors supports and ties shall be non-combustible and corrosion-resistant.


Section 1204
Enclosure of Vertical Openings

(a) General. Vertical openings shall be enclosed depending upon the fire-resistive requirements of a particular type of construction as set forth in this Code.

(b) Elevator Enclosures. Walls and partitions enclosing elevators and escalators shall be of not less than the fire-resistive construction required under the Types of Construction. Enclosing Walls of elevator shafts may consist of wire glass set in metal frames on the entrance side only. Elevator shafts extending through more than two storeys shall be equipped with an approved means of adequate ventilation to and through the main roof of the building: Provided, that in those buildings housing Groups F and G Occupancies equipped with automatic fire-extinguishing systems throughout, enclosures shall not be required for escalators: Provided, further that the top of the escalator opening at each storey shall be provided with a draft curtain. Such draft curtain shall enclose the perimeter of the unenclosed opening and shall extend from the ceiling downward at least 300 millimeters on all sides.

Automatic sprinkles shall be provided around the perimeter of the opening and within a 600 millimeters of the draft curtain. The distance between the sprinkles shall not exceed 1.80 meters center-to-center.

(c) Other Vertical Openings. All shafts, ducts, chutes, and other vertical openings not covered in paragraph (b) above shall have enclosing walls conforming to the requirements specified under the type of construction of the building in which they are located.

In other than Group A Occupancies rubbish and linen chutes shall terminate in rooms separated from the remainder of the building by a One-Hour Fire-Resistive Occupancy Separation. Openings into the chutes shall not be located in required exit corridors or stairways.

(d) Air Ducts. Air ducts passing through a floor shall be enclosed in a shaft. The shaft shall be as required in this Code for vertical openings. Dampers shall be installed where ducts pierce the shaft enclosure walls. Air ducts in Group A Occupancies need not be enclosed in a shaft if conforming to the mechanical provisions of this Code.


Section 1205
Floor Construction

(a) Floors shall be of such materials and construction as specified under Chapter 5 Fire- Zones and Fire-Resistive Standards and under Chapter 6 – Types of Construction.

(b) All floors shall be so framed and secure into the framework and supporting walls as to form an integral part of the whole building.

(c) The types of floor construction used shall provide means to keep the beam and girders from lateral buckling.


Section 1206
Roof Construction and Covering

(a) Roof Covering. Roof covering for all buildings shall be either fire-retardant or ordinary depending upon the fire-resistive requirements of the particular type of construction. The use of combustible roof insulation shall be permitted in all types of construction provided it is covered with approved roof covering applied directly thereto.

(b) Roof Trusses. All roofs shall be so framed and tied into the framework and supporting walls so as to form an integral part of the whole building. Roof trusses shall have all joints well fitted and shall have all tension members well tightened before any load is placed in the truss. Diagonal and sway bracing shall be used to brace all roof trusses. The allowable working stresses of materials in trusses shall conform to this Code. Camber shall be provided to prevent sagging.

(c) Attics

(1) Access. An attic access opening shall be provided in the ceiling of the top floor of buildings with a combustible ceiling or roof construction. The opening shall be located in a corridor or hallway of buildings of three or more storeys in height, and readily accessible in buildings of any height. An opening shall not be less than 600 millimeters square or 600 millimeters in diameter. The minimum clear headroom of 800 millimeters shall be provided above the access opening.

For ladder requirements, refer to the Philippine Mechanical Engineering Code.

(2) Area Separation. Enclosed attic spaces of combustible construction shall be divided into horizontal areas not exceeding 250 square meters by fire-resistive partitions extending from the ceiling to the roof. Except, that where the entire attic is equipped with an approved automatic fire-extinguishing system, the attic space may be divided into areas not to exceed 750 square meters. Openings in the partitions shall be protected by self-closing doors.

(3) Draft Stops. Regardless of the type of construction, draft stops shall be installed in trusses roofs, between roof and bottom chords or trusses, in all buildings exceeding 2000 square meters. Draft stops shall be constructed as for attic area separations.



(4) Ventilation. Enclosed attics including rafter spaces formed where ceilings are applied direct to the underside or roof rafters, shall be provided with adequate ventilation protected against the entrance of rain.

(d) Roof Drainage System

(1) Roof Drains. Roof drains shall be installed at low points of the roof and shall be adequate in size to discharge all tributary waters.

(2) Overflow Drains and Scuppers. Where roof drains are required, adequate overflow drains shall be provided.

(3) Concealed Piping. Roof drains and overflow drains, when concealed within the construction of the building, shall be installed in accordance with the provisions of the National Plumbing Code.

(4) Over Public Property. Roof drainage water from a building shall not be permitted to flow over public property, except for Group A and J Occupancies.

(e) Flashing. Flashing and counter flashing shall be provided at the juncture of the roof and vertical surfaces.


Section 1207
Stairs, Exits and Occupant Loads

(a) General. The construction of stairs and exits shall conform to the occupant load requirements of buildings, reviewing stands, bleachers and grandstands:

(1) Determinations of Occupant Loads. The Occupant load permitted in any building or portion thereof shall be determined by dividing the floor area assigned to that use by the unit area allowed per occupant as determined by the Secretary.

(2) Exit Requirements. Exit requirements of a building or portion thereof used for different purposes shall be determined by the occupant load which gives the largest number of persons. No obstruction shall be placed in the required width of an exit except projections permitted by this Code.

(3) Posting of Room Capacity. Any room having an occupant load of more than 50 where fixed seats are not installed, and which is used for classroom, assembly, or similar purpose shall have the capacity of the room posted in a conspicuous place near the main exit from the room.

(4) Changes in Elevation. Except in Groups A Occupancies, changes in floor elevations of less than 300 millimeters along any exit serving a tributary occupant load of 10 or more shall be by means of ramps.

(b) Exits

(1) Number of Exits. Every building or usable portion thereof shall have at least one exit. In all occupancies, floors above the first storey having an occupant load of more than 10 shall not have less than two exits. Each mezzanine floor used for other than storage purposes, if greater in area than 185 square meters or more than 18.00 meters in any dimension, shall have at least than two stairways to an adjacent floor.

Every storey or portion thereof, having an occupant load of 500 to 999 shall have at least three exits. Every storey or portion thereof having an occupant load of 1000 or more shall have at least four (4) exits. The number of exits required from any storey of a building shall be determined by using the occupant loads of floors which exit through by using the occupant loads of floors which exit through the level under consideration as follows: 50 percent of the occupant load in the first adjacent storey above (and the first adjacent storey below, when a storey below exits through the level under consideration) and 25 percent of the occupant load in the storey immediately beyond the first adjacent storey. The maximum number of exits required for any storey shall be maintained until egress is provided from the structures. For purposes of this Section basement or cellars and occupied roofs shall be provided with exits as required for storeys. Floors above the second storey, basements and cellars used for other than service of the building shall have not less than two exits.

(2) Width. The total width of exits in meters shall not be less than the total occupant load served divided by 165. Such width of exits shall be divided approximately equally among the separate exits. The total exit width required from any storey of a building shall be determined by using the occupant load of that storey plus the percentage of the occupant loads of floors which exits through the level under consideration as follows: fifty (50) per cent of the occupant load in the first adjacent storey above (and the first adjacent storey below when a storey below exits through the level under consideration) and twenty five per cent of the occupant load in the storey immediately beyond the first adjacent storey. The maximum exit width from any storey of a building shall be maintained.

(3) Arrangement of Exits. If only two exits are required they shall be placed a distance apart to not less than one-fifth of the perimeter of the area served measured in a straight line between exits. Where three or more exits are required they shall be arranged a reasonable distance apart so that if one becomes blocked, the others will be available.

(4) Distance to Exits. No point in a building without a sprinkle system shall be more than 45.00 meters from an exterior exit door, a horizontal exit, exit passageway, or an enclosed stairway, measured along the line of travel. In a building equipped with a complete automatic fire extinguishing system the distance from exits may be increased to 60.00 meters.

(c) Doors. The provisions herein shall apply to every exit door serving an area having an occupant load of more than 10 or serving hazardous rooms or areas.

(1) Swing. Exit door shall swing in the direction of exit travel when serving any hazardous areas or when serving an occupant load of 50 or more. Double acting doors shall not be used as exits serving a tributary occupant load of more than 100; nor shall they be used as a part of fire assembly, nor equipped with public hardware. A double acting door shall be provided with a view panel of not less than 1,300 square centimeters.

(2) Type of Lock or Latch? Exit door shall be openable from the inside without the use of a key or any special knowledge or effort:

Except, that this requirement shall not apply to exterior exit doors in a Group E or F Occupancy if there is a conspicuous, readily visible and durable sign on or adjacent to the door, stating that the door is to remain unlocked during business hours. The locking device must be of a type that will readily be distinguishable as locked. Flush bolts or surface bolts are prohibited.

(3) Width and Height. Every required exit doorway shall be of a size as to permit the installation of a door not less than 900 millimeters in width and not less than 2.00 meters in height. When installation in exit doorways, exit doors shall be capable of openings at least 90 decrees and shall be so mounted that the clear width of the exit way is not less than 700 millimeters. In computing the required exit width the net dimension of the exitway shall be used.

(4) Door Leaf Width. No leaf of an exit door shall exceed 1.20 meters in width.

(5) Special Doors. Revolving, sliding, and overhead doors shall not be used as required exits.

(6) Egress from Door. Every required exit door shall give immediate access to an approved means of egress from the building.

(7) Change in Floor Level at Doors. Regardless of the occupant load there shall be a floor or landing on each side of an exit door. The floor or landing shall be leveled with, or not more than 50 millimeters lower than the threshold of the doorway: Except, that in Group A and B occupancies, a door may open on the top step of a flight of stairs or an exterior landing provided the door does not swing over the top step or exterior landing and the landing is not more than 200 millimeters below the floor level.

(8) Door Identification. Glass doors shall conform to the requirements in Section 1005. Other exit doors shall be so marked that they are already distinguishable from the adjacent construction.

(9) Additional Doors. When additional doors are provided for egress purposes, they shall conform to all provisions in the following cases: Approved revolving doors having leaves which will collapse under opposing pressures may be used in exit situations: Provided: That such doors have a minimum width of 2.00 meters or they are not used in occupancies where exits are required to be equipped with panic hardware or at least one conforming exit door is located adjacent to each revolving doors installed in a building and the revolving door shall not be considered to provide any exit width.

(d) Corridors and Exterior Exit Balconies. The provisions herein shall apply to every corridor and exterior exit balcony serving as required exit for an occupant load of more than ten.

(1) Width. Every corridor or exit balcony shall not be less than 1.10 meters in width.

(2) Projections. The required width of corridors and exterior exit balconies shall be an obstructed: Except that trim handrails, and doors when fully opened shall not reduce the required width by more than 200 millimeters. Doors in any position shall not reduce the required width of the corridor by more than one-half.

(3) Access to Exits. When more than one exit is required, they shall be arranged to allow going to either direction from any point dead ends permitted by this Code.

(4) Dead Ends. Corridors and exterior exit balconies with dead ends are permitted when the dead end does not exceed 6.00 meters in length.

(5) Construction. Walls and ceilings of corridors shall not be less than one-hour fire-resistive construction. Provided, that this requirement shall not apply to exterior exit balconies, railings, and corridors of one-storey building housing a Group E and F Occupancy occupied by one tenant only and which serves an occupant load of 30 or less, nor to corridors, formed by temporary partitions. Exterior exit balconies cannot project into an area where protected openings are required.

(6) Openings. When corridor wall are required to be one-hour fire-resistive construction, every interior door opening shall be protected as set forth in generally recognized and accepted requirements for dual purpose fire exit doors. Other interior openings except ventilation louvers equipped with approved automatic fire shutter shall be 7 millimeters thick fixed wire glass set in steel frames. The total area of all openings other than doors, in any portion of an interior corridor wall shall not exceed twenty-five percent of the area of the corridor wall of the room being separated from the corridor.

(e) Stairways. Except stairs or ladders used only to access, equipment, every stairway serving any building or portion thereof shall conform to the following requirements:

(1) Width. Stairways serving an occupant load of more than 50 shall not be less than 1.10 meters. Stairways serving an occupant load of 50 or less may be 900 millimeters wide. Private stairways serving an occupant load of less than 10 may be 750 millimeters. Trim and handrails shall not reduce the required width by more than 100 millimeters.

(2) Rise and Run. The rise of every step in a stairway shall not exceed 200 millimeters and the run shall not less than 250 millimeters. The maximum variations in the height of risers and the width of treads in any one flight shall be 5 millimeters: Except, in case of private stairways serving an occupant load of less than 10, the rise may be 200 millimeters and the run may be 250 millimeters, except as provided in sub-paragraph (3) below.

(3) Winding Stairways. In Group A Occupancy and in private stairways in Group B Occupancies, winders may be used if the required width of run is provided at a point not more than 300 millimeters from the side of the stairway where the treads are narrower but in no case shall any width of run be less than 150 millimeters at any point.

(4) Circular Stairways. Circular stairs may be used as an exit provided the minimum width of run is not less than 250 millimeters. All treads in any one flight between landings shall have identical dimensions within a 5 millimeter tolerance.

(5) Landing. Every landing shall have a dimension measured in the direction of travel equal to the width of the stairway. Such dimension need not exceed 1.20 meters when the stairs has a straight run. Landings when provided shall not be reduced in width by more than 100 millimeters by a door when fully open.

(6) Basement Stairways. Where a basement stairway and a stairway to an upper storey terminate in the same exit enclosure, an approved barrier shall be provided to prevent persons from continuing on to the basements. Directional exit signs shall be provided as specified in this Code.

(7) Distance between Landings. There shall be not more than 3.60 meters vertical distance between landings.

(8)  Handrails. Stairways shall have handrails on each side and every stairway required to be more than 3.00 meters in width shall be provided with not less than one intermediate handrail for each 3.00 meters of required width. Intermediate handrail shall be spaced approximately equal within the entire width of the stairway. Handrails shall be placed not less than 800 millimeters nor more than 900 millimeters above the nosing of treads and ends of handrails shall be returned or shall terminate in newel posts or safety terminals: Except, in the following cases: Stairways 1.10 meters or less in width and stairway serving one individual dwelling unit in Group A or B Occupancies may have one handrail, except that such stairway open on one or both sides shall have handrails provided on the open side or sides: or stairway having less than four risers need not have handrails.

(9) Exterior Stairway Protection. All openings in the exterior wall below or within 3.00 meters, measured horizontally of an exterior exit stairway serving a building over two storeys in height shall be protected by a self-closing fire assembly having a three-fourths hour fire-resistive rating: Except, that opening may be unprotected when two separated exterior stairways serve an exterior exit balcony.

(10) Stairway Construction-Exterior. Exterior stairway shall be of incombustible material: Except, that on Type III buildings which do not exceed two storeys in height, which are located in less fire-restrictive Fire Zones, as well as on Type I buildings may be of wood not less than 50 millimeters in nominal thickness. Exterior stairs shall be protected as required for exterior walls due to location on property as specified in this Code. Exterior stairways shall not project into an area where openings are required to be protected. Where there is enclosed usable space under stairs, the walls and soffits of the enclosed space shall be protected on the enclosed side as required for one-hour fire-resistive construction.

(11)  Stairway to Roof. In every building four or more storeys in height, one stairway shall extend to the roof unless the roof has C slope greater than 1 in 3.

(12) Headroom. Every required stairway shall have a headroom clearance of not less than 2.00 meters. Such clearance shall be established by measuring vertically from a plane parallel and tangent to the stairway tread nosing to the soffit above all points.

(f) Ramps. A ramp conforming to the provisions of this Code may be used as an exit. The width of ramps shall be as required for corridors.

(g) Horizontal Exit. If conforming to the provisions of this Code, a horizontal exit may be considered as the required exit. All openings in a separation wall shall be protected by a fire assembly having a fire-resistive rating not less than the occupant load served by such exit. The capacity shall be determined by allowing 0.30 square meter of net floor area per ambulatory occupant and 1.90 square meters per non-ambulatory occupant. The dispersal area into which the horizontal exit loads shall be provided with exits as required by this Code.

(h) Exit Enclosures. Every interior stairway, ramp, or escalator shall be enclosed as specified in this Code: Except, that in other than Group D Occupancies, as an enclosure will not be required for stairway, ramp, or escalator serving only one adjacent floor and not connected with corridors or stairways serving other floors. Stairs in Group A Occupancies need not be enclosed.

(1) Enclosure walls shall not be less than two-hour fire-resistive construction. There shall be no openings into exit enclosures except exit doorways and openings in exterior walls. All exit doors in an exit enclosure shall be appropriately protected.

(2) Stairway and ramp enclosures shall include landings and parts of floors connecting stairway flights and shall include a corridor on the ground floor leading from the stairway to the exterior of the building. Enclosed corridors of passageways are not required from unenclosed stairways.

(3) A stairway in an exit enclosure shall not continue below the grade level exit unless an approved barrier is provided at the ground floor level to prevent persons from accidentally continuing into the basement.

(4) There shall be no enclosed usable space under stairways in an exit enclosure, nor shall the open space under such stairways be used for any purpose.

(i) Smoke proof Enclosures

A smokeproof enclosure shall consist of a vestibule and a continuous stairway enclosed from the highest point to the lowest point by walls of two-hour fire-resistive construction. In building five storeys or more height, one of the required exits shall be a smokeproof enclosure.

(1) Stairs in smokeproof enclosures shall be of incombustible construction.

(2) There shall be no openings in smokeproof enclosures, except exit doorways and openings in exterior walls. There shall be no openings directly into the interior of the building. Access shall be through a vestibule with one wall at least fifty percent open to the exterior and having an exit door from the interior of the building and exit door leading to the smokeproof enclosure. In lieu of a vestibule, access may be by way of an open exterior balcony of incombustible materials.

(3) The opening from the building to the vestibule or balcony shall be protected with a self-closing fire assembly having one-hour fire-resistive rating. The opening from the vestibule or balcony to the stair tower shall be protected by a self-closing fire assembly having a one-hour fire-resistive rating.

(4) A smokeproof enclosure shall exit into a public way or into an exit passageway leading to a public way. The exit passageway shall be without other openings and shall have walls, floors, and ceilings of two-hour fire-resistance.

(5) A stairway in a smokeproof enclosure shall not continue below the grade level exit unless an approved barrier is provided at a ground floor level to prevent persons from accidentally walking into the basement.

(j)  Exit Outlets, Courts, and Passageways

Every exit shall discharge into a public way, exit court, or exit passageway. Every exit court shall discharge into a public way or an exit passageway. Passageways shall be without openings other than required exits and shall have walls, floors, and ceilings of the same period of fire-resistance as the walls, floors and ceilings of the building but shall not be less than one-hour fire-resistive construction.

(1) Width

Every exit court and exit passageway shall be at least as wide as the required total width of the tributary exits, such required width being based on the occupant load served. The required width of exit courts or exit passageway shall be unobstructed except as permitted in corridors.

At any point where the width of an exit court is reduced from any cause, the reduction in width shall be affected gradually by a guardrail at least 900 millimeters in height. The guardrail shall make an angle of not more than 30 degrees with the axis of the exit court.

(2) Slope

The slope of exit courts shall not exceed 1 in 10. The slope of exit passageway shall not exceed 1 in 8.

(3) Number of Exits

Every exit court shall be provided with exits as required in this Code.

(4) Openings

All openings into an exit court less than 3.00 meters wide shall be protected by fire assemblies having not less than three-fourth hour fire-resistive rating. Except, that openings more than 3.00 meters above the floor of the exit court may be unprotected.

(k) Exit Signs and Illuminations

Exits shall be illuminated at any time the building is occupied with light having an intensity of not less than 10.7 lux at floor level: Except, that for Group A Occupancies, the exit illumination shall be provided with separate circuits or separated sources of power (but not necessarily separate from exit signs when these are required for exit signs illumination).

(1) Aisles

Every portion of every building in which are installed seats, tables, merchandise, equipment, or similar materials shall be provided with aisles leading to an exit.

(2) Width

Every aisle shall be not less than 800 millimeters wide if serving only one side, and not less than 1 meter wide if serving both sides. Such minimum width shall be measured at the point farthest from an exit, crosssle, or foyer and shall be increased by 30 millimeters for every meters in length towards the exit, crosssle or foyer.

(3) Exit Distance

In areas occupied by seats and in Groups H and I Occupancies without seats, the line travel to an exit door by ansle shall be not more than 45.00 meters. With standard spacing, as specified in this Code, aisles shall be so located that there will be not more than seven seats between the wall and ansle and not more than fourteen seats between aisles. The number of seats between aisles may be increased to 30 where exit doors are provided along each side aisle of the row of seats at the rate of one pair of exit doors for every five rows of seats, provided further that the distance between seats back to back is at least one meter. Such exit doors shall provide a minimum clear width of 1.70 meters.

(4) Cross Aisles

Aisles shall terminate in a cross aisle, foyer, or exit. The width of the cross aisle shall be not less than the sum of the required width of the widest aisle plus fifty percent of the total required width of the remaining aisle leading thereto. In Groups C, H and E Occupancies, aisles shall not be provided a dead end greater than 6.00 meters in length.

(5) Vomitories

Vomitories connecting the foyer or main exit with the cross aisles shall have a total width not less than the sum of the required width of the widest aisles leading thereto plus fifty percent of the total required width of the remaining aisles leading thereto.

(6) Slope

The slope portion of aisle shall not exceed a fall 1 in 8.

(l) Seats

(1) Seat Spacing

With standard seating, the spacing of rows of seats from back-to-back shall not less than 840 millimeters. With continental seating, the spacing of rows of unoccupied seat shall provide a clear width measured horizontally, as follows: 450 millimeters clear for rows of 18 seats or less; 500 millimeters clear for rows of 35 seats or less; 525 millimeters clear for rows of 45 seats or less; and 550 millimeters clear for rows of 46 seats or more.

(2) Width

The width if any seat be not less than 450 millimeters.

(m) Reviewing Stands, Grandstands, and Bleachers

(1) Height of Stands

Stands made of combustible framing shall be limited to 11 rows or 2.70 meters in height.

(2) Design Requirements

The minimum unit live load for reviewing stands, grandstands, and bleachers shall be 500 kilograms per square meter of horizontal projection for the structure as a whole. Seat and footboards shall be 180 kilograms per linear meter. The sway force, applied to seats, shall be 35 kilograms per linear meter parallel to the seats and 15 kilograms per linear meter perpendicular to the seats. Sway forces need not to be applied simultaneously with other lateral forces.

(3) Spacing Seats

(a) Row spacing

The minimum spacing of rows of seats measured from back-to-back shall be: 600 millimeters for seats without backrests in open air stands; 750 millimeters for seats with backrests, and 850 millimeters for chair seating.

There shall be a space of not less than 300 millimeters between the back of each seat and the front of the seat immediately behind it.

(b) Rise Between Rows

The maximum rise from one row of seats to the next shall not exceed 400 millimeters.

(c) Seating Capacity

For determining the seating capacity of a stand the width of any seat shall not be less than 450 millimeters nor more than 480 millimeters.

(d) Number of Seats Between Aisles

The number of seats between any seat and an aisle shall not be greater than 15 for open air stands with seats without backrests in buildings.

(4) Aisles

(a) Aisles Required

Aisles shall be provided in all stands: except, that aisles may be omitted when all the following conditions exists; Seats are without backrests; the rise from row to row does not exceed 300 millimeters per row; the number of rows does not exceed 11 in height; the top seating board is not over 3.00 meters above grade; and the first seating board is not more than 500 millimeters above grade.

(b) Obstructions

No obstruction shall be placed in the required width of any aisle or exitway.

(c) Stairs Required

When an aisle is elevated more than 200 millimeters above grade, the aisle shall be provided with a stairway or ramp whose width is not less than the width of the aisle.

(d) Dead End

No vertical aisle shall have a dead end more than 16 rows in depth regardless of the number of exits required.

(e) Width

Aisles shall have a minimum width of 1.10 meters.

(5) Stairs and Ramps

The requirements in this Code shall apply to all stairs and ramps except for portions that pass through the seating area.

(a) Stair Rise and Run

The maximum rise of treads shall not exceed 200 millimeters and the minimum width of the run shall be 280 millimeters. The maximum variation in the width of treads in any one flight shall not be more than 5 millimeters and the maximum variation in one height of two adjacent rises shall not exceed 5 millimeters.

(b) Ramp Slope

The slope of a ramp shall not exceed 1 in 8. Ramps shall be roughened or shall be of approved nonslip material.

(c) Handrails

A ramp with a slope exceeding 1 in 10 shall have handrails. Stairs for stands shall have handrails. Handrails shall conform to the requirements of this Code.

(6) Guardrails

(a) Guardrails shall be required in all locations where the top of a seat plank is more than 1.20 meters above the grade and at the front of stands elevated more than 600 millimeters above grade. Where only sections of stands are used, guardrails shall be provided as required in this Code.

(b) Railings shall be 1.10 meters above the rear of a seat plank or 1.10 meters above the rear of the steps in the aisle when the guardrail is parallel and adjacent to the aisle: Except, that the height may be reduced to 900 millimeters for guardrails located in front of the grandstand.

(c) A midrail shall be placed adjacent to any seat to limit the open distance above the top of any part of a seat to 250 millimeters where the seat is at the extreme end or at the extreme rear of the bleachers or grandstand. The intervening space shall have one additional rail midway in the opening: Except, that railings may be omitted when stands are placed directly against a wall or fence giving equivalent protection; stairs and ramps shall be provided with guardrails. Handrails at the front of stands and adjacent to an aisle shall be designed to resist a load of 75 kilograms per linear meter applied at the top rail. Other handrails shall be designed to resist a load of 40 kilograms per linear meter.

(7) Foot Boards

Footboards shall be provided for all rows of seats above the third row or beginning at such point where the seating plank is more than 600 millimeters above grade.

(8) Exits

(a) Distance to Exit

The line of travel to an exit shall not be more than 45.00 meters. For stands with seats without backseats this distance may be measured by direct line from a seat to the exit from the stand.

(b) Aisle Used as Exit

An aisle may be considered as only one exit unless it is continuous at both ends to a legal building exit or to a safe dispersal area.

(c) Two Exits Required

A stand with the first seating board not more than 500 millimeters above grade of floor may be considered to have two exits when the bottom of the stand is open at both ends. Every stand or section of a stand within a building shall have at least two means of egress when the stand accommodates more than 50 persons. Every open air stand having seats without backrest shall have at least two means of egress when the stand accommodates more than 300 persons.

(d) Three Exits Required

Three exits shall be required for stands within a building when there are more than 300 occupants within a stand and for open air stands with seats without backrests where a stand or section of a stand accommodates more than 1000 occupants.

(e) Four Exits Required

Four exits shall be required when a stand or section of a stand accommodates more than 1000 occupants: Except, that for an open air stand with seats without backrests four exits need not be provided unless there are accommodations for more than 3000 occupants.

(f) Width

The total width of exits in meters shall not be less than the total occupant load served divided by 165: Except, that for open air stands with seats without backrests the total width of exits in meter shall not be less than the total occupant load served divided by 500 when existing by stairs, and divided by 650 when existing by ramps or horizontally. When both horizontal and stair exits are used, the total width of exits shall be determined by using both figures as applicable. No exit shall be less than 1.10 meters in width. Exits shall be located at a reasonable distance apart. When only two exits are provided, they shall be spaced not less than one-fifth of the perimeter apart.

(9) Securing of Chairs

Chairs and benches used on raised stands shall be secured to the platforms upon which they are placed: Except, that when less than 25 chairs are used upon single raised platform the fastening of seat to the platform may be omitted. When more than 500 loose chairs are used in connection with athletic events, chairs shall be fastened together in groups of not less than three, and shall be tied or staked to the ground.

(10) Safe Dispersal Area

Each safe dispersal area shall have at least two exits. If more than 6000 persons are to be accommodated within such an area, there shall be a minimum of three exits, and for more than 9000 persons there shall be a minimum of four exits. The aggregate clear width of exits from a safe dispersal area shall be determined on the bases of not less than one exit unit of 600 millimeters for each 500 persons to be accommodated and not exit shall be less than 1.10 meters in width, a reasonable distance apart that shall be spaced not less than one-fifth of the perimeter of the area apart from each other.

(n)  Special Hazards

(1) Boiler Rooms

Except in Group A Occupancies, every boiler room and every room containing an incinerator or liquified petroleum gas or liquid fuel-fired equipment shall be provided with at least two means of egress, one of which may be a ladder. All interior openings shall be protected as provided for in this Code.

(2) Cellulose Nitrate Handling

Film laboratories, projection rooms, and nitro-cellulose processing rooms shall have not less than two exits.


Section 1208
Skylights

(a) All skylights shall be constructed with metal frames except those for Groups A and J Occupancies. Frames of skylights shall be designed to carry loads required for roofs. All skylights, the glass of which is set at an angle of less than 45 degrees from the horizontal, if located above the first storey, shall be set at least 100 millimeters above the roof. Curbs on which the skylights rest shall be constructed of incombustible materials except for Types 1 or 11 Construction.

(b) Spacing between supports in one direction for flat wired glass in skylights shall not exceed 625 millimeters. Corrugated wired glass may have supports 1.50 meters apart in the direction of the corrugation. All glass in skylights shall be wired glass: Except, that skylights over vertical shafts extending through two or more storeys shall be glazed with plain glass as specified in this Code: Provided, that wire glass may be used in ventilation equal to not less than one-eight the cross-sectional area of the shaft but never less than 1.20 meters is provided at the top of such shaft. Any glass not wire glass shall be protected above and below with a screen constructed of wire not smaller than 2.5 millimeters in diameter with a mesh not larger than 25 millimeters. The screen shall be substantially supported below the glass.

(c)  Skylights installed for the use of photographers may be constructed of metal frames and plate glass without wire netting.

(d) Ordinary glass may be used in the roof and skylights for greenhouses, Provided, that height of the greenhouses at the ridge does not exceed 6.00 meters above the grade. The use of wood in the frames of skylights will be permitted in greenhouses outside of highly restrictive Fire Zones if the height of the skylight does not exceed 6.00 meters above the grade, but in other cases metal frames and metal sash bars shall be used.

(e) Glass used for the transmission of light, if placed in floors or sidewalks, shall be supported by metal or reinforced concrete frames, and such glass shall not be less than 12.5 millimeters in thickness. Any such glass over 100 square centimeters in area shall have wire mesh embedded in the same or shall be provided with a wire screen underneath as specified for skylights in this Code. All portions of the floor lights or sidewalk lights shall be of the same strength as required for floor is surrounded by a railing not less than 1.10 meters in height, in which case the construction shall be calculated for not less than roof loads.


Section 1209
Bays, Porches, and Balconies

(a) Walls and floors in bay and oriel windows shall conform to the construction allowed for exterior walls and floors of the type of construction of the building to which they are attached. The roof covering of a bay or oriel window shall conform to the requirements of the roofing of the main roof. Exterior balconies attached to or supported by wall required to be of masonry, shall have brackets or beams constructed of incombustible materials. Railings shall be provided for balconies, landings, or porches which are more than 750 millimeters above grade.


Section 1210
Penthouses and Roof Structures

(a)  Height

No penthouse or other projection above the roof in structures of other than Type V construction shall exceed 8.40 meters above the roof when used as an enclosure for tanks or for elevators which run to the roof and in all other cases shall not extend more than 3.60 meters in height with the roof.

(b) Area

The aggregate area of all penthouses and other roof structures shall not exceed one third of the area of the supporting roof.

(c) Prohibited Uses

No penthouse, bulkhead, or any other similar projection above the roof shall be used for purposes other than shelter of mechanical equipment or shelter of vertical shaft openings in the roof. A penthouse or bulkhead used for purposes other than that allowed by this Section shall conform to the requirements of this Code for an additional storey.

(d) Construction

Roof structures shall be constructed with walls, floors, and roof as required for the main portion of the building except in the following cases:

(1) On Types III and IV constructions, the exterior walls and roofs of penthouses which are 1.50 meters or more from an adjacent property line may be of one-hour fire-resistive incombustible construction.

(2) Walls not less than 1.50 meters from an exterior wall of a type IV construction may be of one-hour fire-resistive incombustible construction. The above restriction shall not prohibit the placing of wood flagpoles or similar structures on the roof of any building.

(e) Towers and Spires

Towers and spires when enclosed shall have exterior walls as required for the building to which they attached. Towers not enclosed and which extend more than 20.00 meters above the grade shall have their framework constructed of iron, steel, or reinforced concrete. No tower or spire shall occupy more than one-fourth of the street frontage of any building to which it is attached and in no case shall the base area exceed 150 square meters unless it conforms entirely to the type of construction requirements of the building to which it is attached and is limited in height as main part of the building. If the area of the tower and spire exceeds 10.00 square meters any horizontal cross section, its supporting frames shall extend directly to the ground. The roof covering of the spires shall be as required for the main room of the rest of the structure. Skeleton towers used as radio masts, neon signs, or advertisement frames and placed on the roof of any building shall be constructed entirely of incombustible materials when more than 7.50 meters in height, and shall be directly supported on an incombustible framework to the ground. No such skeleton towers shall be supported on roofs of combustible framings. They shall be designed to withstand a wind load from any direction in addition to any other loads.


Section 1211
Chimneys, Fireplaces, and Barbecues

(a) Chimneys

(1) Structural Design

Chimneys shall be designed, anchored, supported, reinforced, constructed, and installed in accordance with generally accepted principles of engineering. Every chimney shall be capable of producing a draft at the appliance not less than that required for the safe operation of the appliance connected thereto. No Chimney shall support any structural load other than its own weight unless it is designed to act as a supporting member. Chimneys in a wood-framed building shall be anchored laterally at the ceiling line and at each floor line which is more than 1.80 meters above grade, except when entirely within the framework or when designed to be free standing.

(2) Walls

Every masonry chimney shall have walls of masonry units, bricks, stones, listed masonry chimney units, reinforced concrete or equivalent solid thickness of hollow masonry and lined with suitable liners in accordance with the following requirements:

(a) Masonry Chimneys for Residential Type Appliances

Masonry chimneys shall be constructed of masonry units or reinforced concrete with walls not less than 100 millimeters thick; or of rubble stone masonry not less than 300 millimeters thick. The chimney liner shall be in accordance with this Code.

(b) Masonry Chimneys for Low Heat Appliances

Masonry chimneys shall be constructed of masonry units or reinforced concrete with walls not less than 200 millimeters thick: Except, that rubble stone masonry shall be not less than 300 millimeters thick. The chimney liner shall be in accordance with this Code.

(c) Masonry Chimneys for Medium-Heat Appliances

Masonry chimneys for medium-heat appliances shall be constructed of solid masonry units of reinforced concrete not less than 200 millimeters thick, Except, that stone masonry shall be not less than 300 millimeters thick and, in addition shall be lined with not less than 100 millimeters of firebrick laid in a solid bed of fire clay mortar with solidly filled head, bed, and wall joints, starting not less than 600 millimeters below the chimney connector entrance. Chimneys extending 7.50 meters or less above the chimney connector shall be lined to the top.

(d) Masonry Chimneys for High-Heat Appliances

Masonry chimneys for high-heat appliances shall be constructed with double walls of solid masonry units or reinforced concrete not less than 200 millimeters in thickness, with an air space of not less than 50 millimeters between walls. The inside of the interior walls shall be of fire-brick not less than 100 millimeters in thickness laid in a solid bed of fire clay mortar with solidly filled head, bed, and wall joints.

(e) Masonry Chimneys for Incinerators Installed in Multi-Storey Buildings (Apartment-Type Incinerators) Chimneys

For incinerators installed in multi-storey building using the chimney passageway as a refuse chute where the horizontal grate area of combustion chamber does not exceed 0.80 square meter shall have walls of solid masonry or reinforced concrete, not less than 100 millimeters thick with a chimney lining as specified in this Code. If the grate area of such an incinerator exceeds 0.80 square meter, the walls shall not be less than 100 millimeters of firebrick except that higher than 9.00 meters above the roof of the combustion chamber, common brick alone 200 millimeters in thickness, may be used.

(f) Masonry Chimneys for Commercial and Industrial Type Incinerators

Masonry chimneys for commercial and industrial type incinerators of a size designed for not more than 110 kilograms of refuse per hour and having a horizontal grate area not exceeding 0.50 square meter shall have walls of solid masonry or reinforced concrete not less than 100 millimeters thick with lining of not less than 100 millimeters of firebrick, which lining shall extend for not less than 12.00 meters above the roof of the combustion chamber. If the design capacity of grate area of such an incinerator exceeds 110 kilograms per hour and 0.80 square meter respectively, walls shall not be less than 200 millimeters thick, lined with not less than 100 millimeters of firebrick extending the full height of the chimney.

(3) Linings

Fire clay chimney lining shall not be less than 15 millimeters thick.

The lining shall extend from 200 millimeters below the lowest inlet, or, in the case of fireplace, from the throat of the fireplace to a point above enclosing masonry walls. Fire clay chimney linings shall be installed ahead of the construction of the chimney as it is carried up, carefully bedded one on the other in fire clay mortar, with close-fitting joints left smooth on the inside. Firebrick not less than 500 millimeters thick may be used in place of fire clay chimney.

(4) Area

No chimney passageway shall be smaller in area than the vent connection of the appliance attached thereto.

(5) Height

Every masonry chimney shall extend at least 600 millimeters above the part of the roof through which it passes and at least 600 millimeters above the highest elevation of any part of a building within 3.00 meters to the chimney.

(6) Corbeling

No masonry chimney shall be corbeled from a wall more than 150 millimeters nor shall a masonry chimney be corbeled from a wall which is less than 300 millimeters in thickness unless it projects equally on each side of the wall. In the second storey of a two-storey building of Group A Occupancy, corbeling of masonry chimneys on the exterior of the enclosing walls may equal the wall thickness. In every case the corbeling shall not exceed 25 millimeters protection for each course of brick.

(7) Change in Size or Shape

No change in the size or shape of a masonry chimney shall be made within a distance of 150 millimeters above or below the roof joints or rafters where the chimney passes through the roof.

(8) Separation

When more than one passageway is contained in the same chimney, masonry separation at least 100 millimeters thick bonded into the masonry wall of the chimney shall be provided to separate passageways.

(9) Inlets

Every inlet to any masonry chimney shall enter the side thereof and shall be of not less than 3 millimeters thick metal or 16 millimeters refractory material.

(10) Clearance

Combustible materials shall not be placed within 50 millimeters of smoke chamber or masonry chimney walls when built within a structure, or within 25 millimeters when the chimney is built entirely outside the structure.

(11) Termination

All incinerator chimneys shall terminate in a substantially constructed spark arrester having a mesh not exceeding 20 millimeters.

(12) Cleanouts

Cleanout openings shall be provided at the base of every masonry chimney.

(b)   Fireplaces and Barbecues

Fireplaces, barbecues, smoke chambers and fireplace Chimneys shall be of solid masonry or reinforced concrete and shall conform to the minimum requirements specified in this Code.

(1) Fireplace Walls

Walls of fireplaces shall not be less than 200 millimeters in thickness. Walls of fireboxes shall not be less than 250 millimeters in thickness: Except, that where a lining of firebrick is used, such walls shall not be less than 200 millimeters in thickness. The firebox shall not be less than 200 millimeters in thickness. The firebox shall not be less than 500 millimeters in depth. The maximum thickness of joints in firebrick shall be 10 millimeters.

(2) Hoods

Metal hoods used as part of a fireplace or barbecue shall not be less than No. 18 gauge copper, galvanized iron, or other equivalent corrosion-resistant ferrous metal with all seams and connections of smokeproof unsoldered construction. The goods shall be sloped at an angle of 45 degrees or less from the vertical and shall extend horizontally at least 150 millimeters beyond the limits of the firebox. Metal hoods shall be kept a minimum from combustible materials.

(3) Circulators

Approved metal heat circulators may be installed in fireplaces.

(4) Smoke Chamber

Front and side walls shall not be less than 200 millimeters in thickness. Smoke chamber back walls shall not be less than 150 millimeters in thickness.

(5) Fireplace Chimneys

Walls of chimneys without flue lining shall not be less than 200 millimeters in thickness. Walls of chimneys with flue lining shall not be less than 100 millimeters in thickness and shall be constructed in accordance with the requirements of this Code.

(6) Clearance of Combustible Materials

Combustible materials shall not be placed within 50 millimeters of fireplace, smoke chamber, or chimney walls when built entirely within a structure, or within 25 millimeters when the chimney is built entirely outside the structure. Combustible materials shall not be placed within 150 millimeters of the fireplace opening. No such combustible material within 300 millimeters of the fireplace opening shall project more than 3 millimeters for each 25 millimeters clearance from such opening. No part of metal hoods used as part of a fireplace, barbecue or heating stoves shall be less than 400 millimeters from combustible material. This clearance may be reduced to the minimum requirements set forth in this Code.

(7) Area of Flues, Throats, and Dampers

The net cross-sectional area of the flue and of the throat between the firebox and the smoke chamber of a fireplace shall not be less than the requirements to be set forth by the Board. Where dampers are used, they shall be of not less than No. 12 gauge metal. When fully opened, damper opening shall be not less than ninety percent of the required flue area. When fully open, damper blades shall not extend beyond the line of the inner face of the flue.

(8)  Lintel

Masonry over the fireplace opening shall be supported by a non-combustible lintel.

(9) Hearth

Every fireplace shall be provided with a brick, concrete, stone, or other approved non-combustible hearth slab at least 300 millimeters wider on each side than the fireplace opening and projecting at least 450 millimeters therefrom. This slab shall not be less than 100 millimeters thick and shall be supported by a non-combustible material or reinforced to carry its own weight and all imposed loads.


Section 1212
Fire-Extinguishing Systems

(a) Fire-Extinguishing Systems

When required, standard automatic fire-extinguishing systems shall be installed in the following places, and in the manner provided in this Code.

(1) In every storey, basement or cellar with an area of 200 square meters or more which is used for habitation, recreation, dining, study, or work, and which has an occupant load of more than 20.

(2) In all dressing rooms, rehearsal rooms, workshops or factories, and other rooms with an occupant load of more than 10 or assembly halls under Group H and I occupancies with occupant load of more than 500, and if the next doors of said rooms are more than 30.00 meters from the nearest safe fire dispersal area of the building or opening to an exit court or street.

(3) In all rooms used for storage or handling of photographic x-ray nitrocellulose films and other inflammable articles.

(b) Dry Standpipes

Every building four or more storeys in height shall be equipped with one or more dry standpipes.

(1) Construction and Tests. Dry standpipes shall be of wrought iron or galvanized steel and together with fittings and connections shall be of sufficient strength to withstand 20 kilograms per square centimeter of water pressure when ready for service, without leaking at the joints, valves, or fittings. Tests shall be conducted by the owner of the building contractor in the presence of a representative of the Building Official whenever deemed necessary for the purpose of certification of its proper function.

(2) Size. Dry standpipes shall be of such size as to be capable of delivering 900 liters of water per minute from each of any three outlets simultaneously under the pressure created by one fire engine or pumper based on the standard equipment available.

(3) Number Required. Every building four or more storeys in height where the area of any floor above the third floor is 950 square meters or less, shall be equipped with at least one dry standpipes and an additional standpipe shall be installed for each additional 950 square meters or fraction thereof.

(4) Location. Standpipes shall be located within enclosed stairway landings or near such stairways as possible or immediately inside of an exterior wall and within 300 millimeters of an opening in a stairway enclosure of the balcony or vestibule of a smokeproof tower or an outside exit stairway.

(5)  Siamese Connections. Subject to the provisions of subparagraph (2) all 100 millimeters dry standpipes shall be equipped with a two-way Siamese fire department connection. All 125 millimeter dry standpipes shall be equipped with a three-way Siamese fire department connection and 150 millimeters dry standpipes shall be equipped with a four-way Siamese fire department connection. All Siamese inlet connections shall be located on a street-front of the building and not less than 300 millimeters or more than 1.20 meters above the grade and shall be equipped with a clapper-checks and substantial plugs. All Siamese inlet connections shall be recessed in the wall or otherwise substantially protected.

(6) Outlets. All dry standpipes shall extend from the ground floor to and over the roof and shall be equipped with a 63 millimeters outlet nor more than 1.20 meters above the floor level at each storey. All dry standpipes shall be equipped with a two-way 63 millimeters outlet above the roof. All outlets shall be equipped with gate valves.

(7) Signs. An iron or bronze sign with raised letters at least 25 millimeters high shall be rigidly attached to the building adjacent to all Siamese connections and such signs shall read ; “CONNECTION TO DRY STANDPIPE”.

(c) Wet Standpipes

Every Group H and I Occupancy of any height, and every Group C Occupancy of two more storeys in height and every Group D, D, E, F, and G Occupancy of three or more storeys in height and every Group G and E Occupancy over 1800 square meters in area shall be equipped with one or more interior wet standpipes extending from the cellar or basement into the topmost storey: Provided, that Group H buildings having no stage and having a seating capacity of less than 500 need to be equipped with interior wet standpipes.

(1) Construction. Interior wet standpipes shall be constructed of the same materials as those required for dry standpipes.

(2) Size

(i)    Interior wet standpipes shall have an internal diameter sufficient to deliver 190 liters of water per minute under 2.0 kilograms per square centimeter pressure at the hose connections. Buildings of Group Hand I Occupancy shall have wet standpipes systems capable of delivering the required quantity and pressure from any two outlets simultaneously; for all other occupancies only one outlet need be figured to be opened at one time. In no case shall the internal diameter of a wet standpipe be less than 50 millimeters, except when the standpipe is attached to an automatic fire-extinguishing system.

(ii)   Any approved formula which determined pipe sizes on a pressure drop basis may be used to determine pipe size for wet standpipe systems. The Building Official may require discharge capacity and pressure tests on completed wet standpipe systems.

(3) Number required. The number of wet standpipe when required in this Code shall be so determined that all portions of the building are within 6.00 meters of a nozzle attached to a hose 23.00 meters in length.

(4) Location. In Group H and I Occupancies, outlets shall be located as follows: one on each side of the stage, one at the rear of the auditorium and one at the rear of the balcony. Where occupant loads are less than 500 the above requirements may be waived: Provided, that portable fire-extinguishers of appropriate capacity and type are installed within easy access from the said locations. In Group B, C, D, E, F, and G Occupancies location of all interior wet standpipes shall be in accordance with the requirement for dry standpipes: Provided, that at least one standpipe is installed to cover not more than 650 square meters.

(5) Outlets. All interior wet standpipes shall be equipped with a 38 millimeter valve in each storey, including the basement or cellar of the building, and located not less than 300 millimeters nor more than 1.20 meters above the floor.

(6) Threads. All those threads used in connection with the installation of such standpipes, including valves and reducing fittings shall be uniform with that prescribed by the Secretary.

(7) Water Supply. All interior wet standpipes shall be connected to a street main not less than 100 millimeters in diameter, or when the water pressure is insufficient, to a water tank or sufficient size as provided in subparagraph (8). When more than one interior wet standpipe is required in the building, such standpipe shall be connected at their bases or at their tops by pipes of equal size.

(8)  Pressure and Gravity Tanks. Tanks shall have a capacity sufficient to furnish at least 1,500 liters per minute for period of not less than 10 minutes. Such tanks shall be located so as to provide not less than 2 kilograms per sq. cm. pressure at the topmost base outlet for its entire supply. Discharge pipes from pressure tanks extend 50 millimeters into and above the bottom of such tanks. All tanks shall be tested in place after installation and proved tight at a hydrostatic pressure fifty percent in excess of the working pressure required. Where such tanks are used for domestic purposes the supply pipe for such purposes shall be located at or above the center line of such tanks.

Incombustible supports shall be provided for all such supply tanks and not less than a 900 millimeters clearance shall be maintained over the top and under the bottom of all pressure tanks.

(9) Fire pumps. Fire pumps shall have a capacity of not less than 1,000 liters per minute with a pressure of not less than 2 kilograms per sq. cm. at the topmost hose outlet. The source of supply for such pump shall be a street water main of not less than 100 mm, diameter or a well or cistern containing a one-hour supply. Such pumps shall be supplied with an adequate source of power and shall be automatic in operation.

(10) Hose and Hose Reels. Each hose outlet of all interior wet standpipe shall be supplied with a hose not less than 38 millimeters in diameter. Such hose shall be equipped with a suitable brass or bronze nozzle and shall be not over 23.00 meters in length. An approved standard form of wall hose reel or rack shall be provided for the hose and shall be located so as to make the hose readily accessible at all times and shall be recessed in the walls or protected by suitable cabinets.

(d) Basement Pipe Inlets. Basement pipe inlets shall be installed in the first floor of every store, warehouse, or factory where there are cellars or basements under same:

Except, wherein such cellars or basements there is installed a fire-extinguishing system as specified in this Code or where such cellars or basement are used for banking purposes, safe deposit vaults, or similar uses.

(1) Material. All basement pipe inlets shall be of cast iron, steel, brass, or bronze with lids of cast brass or bronze and shall consist of a sleeve not less than 200 millimeters in diameter through the floor extending to and flush with the ceiling below and with a top flange, recessed with an inside shoulder, to receive the lid and flush with the finished floor surface. The lid shall be a solid casting and shall have a ring lift recessed on the top thereof, so as to flushed. The lid shall have the words “FOR FIRE DEPARTMENT ONLY, DO NOT COVER UP” cast on the top thereof. The lid shall be installed in such a manner as to permit its removal readily from the inlet.

(2) Location. Basement pipe inlets shall be strategically located and kept readily accessible at all times to the Fire Department.

(e) Approval. All fire-extinguishing systems, including automatic sprinklers, wet and dry standpipes, automatic chemical extinguishers, basement pipe inlets, and the appurtenances thereto shall meet the approval of the fire Department as to installation and location and shall be subject to such periodic test as it may require.


Section 1213
Stages and Platform

(a) Stage Ventilators

There shall be one or more ventilators constructed of metal or other incombustible material near the center and above the highest part of any working stage raised above the stage roof and having a total ventilation area equal to at least five percent of the floor area within the stage walls. The entire equipment shall conform to the following requirements:

(1) Opening Action. Ventilators shall open by spring action or force of gravity sufficient to overcome the effects of neglect, rust, dirt, or expansion by heat or wrapping of the framework.

(2) Glass. Glass, if used in ventilators must be protected against falling on the stage. A wire screen, if used under the glass, must be so placed that if clogged it cannot reduce the required ventilating area or interfere with the operating mechanism or obstruct the distribution of water from the automatic fire extinguishing systems.

(3) Design. Ventilators, penthouses, and supporting framework shall be designed in accordance with this Code.

(4) Spring Actuation. Springs, when employed to actuate ventilator doors, shall be capable of maintaining full required tension indefinitely. Springs shall be no stressed more than fifty percent of their rated capacity and shall not be located directly in the air stream, nor exposed to elements.

(5) Location of Fusible Links. A fusible link shall be placed in the cable control system on the underside of the ventilator at or above the roof line or as approved by the Building Official, and shall be so located as not to be affected by the operation of fire-extinguishing systems.

(6) Control. Remote, manual, or electrical control shall provide for both opening and closing of the ventilator doors for periodic testing and shall be located at a point on the stage designated by the Building Official. When remote control of ventilator is electrical, power failure shall not affect its instant operation in the event of fire. Hand winches may be employed to facilitate operation of manually controlled ventilators.

(b) Gridirons

(1) Gridirons, fly galleries, and pin-rails shall be constructed of incombustible materials and fire protection of steel and iron may be omitted. Gridirons and fly galleries shall be designed to support a live load of not less than 367 kilograms per square meter. Each loft block well shall be designed to support 373 kilograms per linear meter and the head block well shall be designed to support the aggregate weight of all the loft block wells served. The head block well must be provided with an adequate strongback or lateral brace to offset torque.

(2) The main counterweight sheave beam shall be designed to support a horizontal and vertical uniformly distributed live load sufficient to accommodate the weight imposed by the total number of loft blocks in the gridiron. The sheave blocks shall be designed to accommodate the maximum load for the loft or head blocks served with a safety factor of five.

(c) Rooms Accessory to Stage

In a building having a stage, the dressing room sections, workshops, and store rooms shall be located on the stage side of the proscenium wall and shall be separated from each other and from the stage by not less than a One-hour Fire Resistive Occupancy Separation.

(d) Proscenium Walls

A stage shall be completely separated from the auditorium by a proscenium wall or not less than two-hour incombustible construction. The proscenium wall shall extend not less than 1.20 meters above the roof over the auditorium. Proscenium walls may have the addition to the main proscenium openings, one opening at the orchestra pit level and not more than two openings at the stage floor level, each of which shall be not more than 2.00 square meters in area. All openings in the proscenium walls of stage shall be protected by a fire assembly having a one and one-half fire-resistive rating. The proscenium opening, which shall be the main opening for viewing performances, shall be provided with a self closing fire-resistive curtain as specified in this Code.

(e) Stage Floor

The type of construction for storage floors shall depend upon the requirements based on the type of Occupancy and the corresponding fire-resistive requirements. All parts of the stage floor shall be designed to support not less than 620 kilograms per square meters. Openings through stage floor shall be equipped with tight-fitting trap doors of wood of not less than 5 millimeters nominal thickness.

(f) Platforms

The type of construction for platforms shall depend upon the requirements based on the type of Occupancy and corresponding fire-resistive requirements. Enclosed platforms shall be provided with one or more ventilators conforming to the requirements of stage ventilators: Except, that the total area shall be equal to five percent of the area of the platform. When more than one ventilator is provided, they shall be so spaced as to provide proper exhaust ventilation. Ventilators shall not be required for enclosed platform having a floor area of 45.00 square meters or less.

(g) Stage Exits

At least one exit not less than 900 millimeters wide shall be provided from each side of the stage opening directly or by means of a passageway not less than 900 millimeters in width to a street or exit court. An exit stair not less than 750 millimeters wide shall be provided for egress from each fly gallery. Each tier of dressing rooms shall be provided with at least two means of egress each not less than 750 millimeters wide and all such stairs shall be constructed in accordance with the requirement specified in this Code. The stairs required in this sub-section need not be enclosed.


Section 1214
Motion Picture Projection Rooms

(a) General. The provisions of this Section shall apply only where ribbon type motion picture films in excess of 22-millimeters width and electric projection equipment are used. Every motion picture machine using ribbon type film in excess of 22 millimeter width and electric arc projections equipment, together with all electrical devices, rheostats, machines, and all such films present in any Group C, I, or H Occupancy, shall be enclosed in a projection room large enough to permit the operator to walk freely on either side and back of the machine.

(b) Construction. Every projection room shall be of not less than one-hour fire-resistive construction throughout and the walls and ceiling shall be finished with incombustible materials. The ceiling shall not be less than 2.40 meters from the finished floor. The room shall have a floor area of not less than 7.00 square meters and 3.50 square meters for each additional machine.

(c) Exit. Every projection room shall have at least two doorways separated by not less than one-thirds the perimeter of the room, each at least 750 millimeters wide and 2.00 meters high. All entrances to a projection room shall be protected by a self-closing fire assembly having a three-fourths hour fire-resistive rating. Such doors shall open outward and lead to proper exits as required in this Code and shall not be equipped with any latch. The maximum width of such door shall be 750 millimeters.

(d) Ports and Openings. Ports in projection room walls shall be of three kinds: projection ports; observation ports; and combination ports used for both observation and for stereopticon, spot or floodlight machines.

(1) Ports Required. There shall be provided for each motion picture projector not more than one projection port, which shall be limited in area to 750 square centimeters, and not more than one observation port, which shall be limited in area to 1,300 square centimeters. There shall be not more than three combination ports, each of which shall not exceed 750 millimeters by 600 millimeters. Each port opening shall be completely covered with a pane of glass; Except, that when acetate safety film is used, projection ports may be increased in size to an area not to exceed 4,500 square centimeters.

(2) Shutters. Each port and every other opening in projection room walls, including, any fresh-air inlets but excluding exit doors and exhaust ducts, shall be provided with a shutter of not less than 2.4 millimeters thick sheet metal or its equivalent large enough to overlap at least 25 millimeters on all sides of such openings. Shutters shall be arranged to slide without binding in guide’s constructed or material equal to the shutters in strength and fire-resistance. Each shutter shall be equipped with a 74ยบ fusible link, which when fused by heat will cause closure of the shutter by gravity. Shutters of a size greater than 1,300 square centimeters shall be equipped with a counter-balance. There shall also be a fusible link located over the upper magazine of each projector, which upon operating will close all the shutters. In addition, there shall be provided suitable means for manually closing all shutters simultaneously from any projector head and from a point within the projection room near each exit door. Shutters may be omitted when only acetate safety film is used.

(e) Ventilation

(1) Inlet. A fresh-air inlet from the exterior of the building not less than 900 square centimeters and protected with wire netting, shall be installed within 50 millimeters of the floor in every projection room, the source of which shall be remote from other outside vents or flues.

(2) Outlets. Ventilation shall be provided by one or more mechanical exhaust systems which shall draw air from each are lamps housing to out-doors either directly or through an incombustible flue used for no other purpose. Exhaust capacity shall not be less than 0.50 cubic meter nor more than 1.40 cubic meter per minute for each arc lamp plus 5.60 cubic meters for the room itself. Systems shall be controlled from within the enclosure and shall have pilot lights to indicate operation.

The exhaust systems serving the projection room may be extended to cover rooms associated therewith such as rewind rooms. No dampers shall be installed in such exhaust systems. Ventilation of these rooms, shall not connected in any way with ventilating or air-conditioning systems serving other portions of the building. Exhaust ducts shall be of incombustible material and shall either be kept 25 millimeters from combustible material or covered with 10 millimeters of incombustible heat-insulating material.

(f) Regulation of Equipment. All shelves, fixtures, and fixed equipment in a projection room shall be constructed of incombustible materials. All films not in actual use shall be stored in metal cabinets having individual compartments for reels or shall be in generally accepted shipping containers. No solders shall be used in the construction of such cabinets.


Section 1215
Lathing, Plastering, and Installation of Wall Boards

The installation of lath, plaster and gypsum wall board shall conform to the fire-resistive rating requirements and the type of construction of building.



CHAPTER XIII
ELECTRICAL AND MECHANICAL REGULATIONS


Section 1301
Electrical Regulations

All electrical systems equipment and installation mentioned in this Code shall conform to the provisions of the Philippine Electrical Code, as adopted by the board of Electrical Engineering pursuant to Republic Act No. 184 otherwise known as the electrical Engineering Law.


Section 1302
Mechanical Regulations

All mechanical systems, equipment and installations mentioned in this Code shall conform to the provisions of the Philippine Mechanical Engineering Code, as adopted by the Board of Mechanical Engineering pursuant to Commonwealth Act No. 294 as amended, otherwise known as the Mechanical Engineering Law.

Part 3 here





No comments :

Post a Comment